parameters vacon • 5524-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com88.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)Code Parameter Min Max Unit Default ID NoteRamp S-shape 0,0 10,0 s 0,0 500 0 = Linear>0 = S-curve ramp timeAcceleration time 1 0,1 3000,0 s 3,0 103Deceleration time 1 0,1 3000,0 s 3,0 104Ramp S-shape 2 0,0 10,0 s 0,0 501Acceleration time 2 0,1 3000,0 s 10,0 502Deceleration time 2 0,1 3000,0 s 10,0 503Flux Braking 0 3 0 5200 = Off1 = Deceleration2 = Chopper3 = Full ModeFlux Braking Cur-rent0,5 xI Nunit2,0 xINunit A I Nunit 519DC Braking Current 0,3 xI Nunit2,0 xINunit A I Nunit 507Defines the currentinjected into the motorduring DC brakeing.Stop DC currenttime 0,00 600,00 s 0,00 508Determines if braking isON or OFF and the brak-ing time of the DC-brakewhen the motor is stop-ping.0 = Not activeStop DC currentfrequency 0,10 10,00 Hz 1,50 515The output frequency atwhich the DC-braking isapplied.Start DC currenttime 0,00 600,00 s 0,00 516 0 = Not activeTable 8.5: Ramps and brakes setupiiiiiiiiiiP4.1P4.2P4.3P4.4P4.5P4.6P4.7P4.8P4.9P4.10P4.11P4.12