92 • vacon parameter descriptionsTel. +358 (0)201 2121 • Fax +358 (0)201 21220599.13.3 Modbus process dataProcess data is an address area for fieldbus control. Fieldbus control is active whenthe value of parameter 2.1 (Control place) is 3 (= fieldbus). The content of the processdata has been determined in the application. The following tables present the proc-ess data contents in the General Purpose Application.Note! 2004 can set as PI Control Reference by setting P15.1(Setpoint se-lection) or 2005 can be set as PI Actual value by setting P15.4(Feed-back value selection)!ID Modbus register Name Scale Type2101 32101, 42101 FB Status Word - Binary coded2102 32102, 42102 FB General Status Word - Binary coded2103 32103, 42103 FB Actual Speed 0,01 %2104 32104, 42104 Output frequency 0.01 +/- Hz2105 32105, 42105 Motor speed 1 +/- Rpm2106 32106, 42106 Motor current 0.01 A2107 32107, 42107 Motor torque 0,1 +/- % (of nomi-nal)2108 32108, 42108 Motor power 0,1 +/- % (of nomi-nal)2109 32109, 42109 Motor voltage 0,1 V2110 32110, 42110 DC link voltage 1 V2111 32111, 42111 Active fault code 1 -Table 9.4: Output process dataID Modbus register Name Scale Type2001 32001, 42001 FB Control Word - Binary coded2002 32002, 42002 FB General Control Word - Binary coded2003 32003, 42003 FB Speed Reference 0,01 %2004 32004, 42004 Programmable by P15.12005 32005, 42005 Programmable by P15.42006 32006, 42006 - - -2007 32007, 42007 - - -2008 32008, 42008 - - -2009 32009, 42009 - - -2010 32010, 42010 - - -2011 32011, 42011 - - -Table 9.5: Input process data