Appendix ï 121Mailbox Command ReferencesWAGO-I/O-SYSTEM 750I/O Modules6.3.5.2 Write the Local Device Name (SetLocalDeviceName, 0x41)With this command, the BluetoothÆ name of the local bus module is set. Thenormal set of ASCII characters is available.NoteThe use of special characters (e.g. word wraps) is possible but should beavoided.The complete device name can be a maximum of 15 characters.The complete device name can be read and written with DLD commandsregardless of the mailbox size.ConditionsMailbox size Operating mode/profile Device role6 12 18 Config. Real-time Ad hoc Master SlaveSaveconfig. Restart(●) (●) ● ● - - ● ● - -RequestByte 27 26 25 24 23 22 21 200 MBX_SETLOCALDEVICENAME1 T -2 MBX_NAME_LENGTH3 CHAR1... ...17 CHAR15ArgumentsParameter Value DescriptionMBX_NAME_LENGTH [1...15] Number of the transferred characters of the nameCHARn Characters of the device name in ASCII codeExample: "ABC"A = CHAR1 = 0x41B = CHAR2 = 0x42C = CHAR3 = 0x43ResponseByte 27 26 25 24 23 22 21 200 MBX_SETLOCALDEVICENAME1 T MBX_RESULT