wc_tx003610gb_FM10.fm136Mobile GeneratorUsing Remote Start Capabilities13.4 Preparing for Automatic/Remote Start-Up (Deep Sea)Background In AUTO mode, the generator can be started remotely, either through a transferswitch or some other type of remote start switch. AUTO mode is the normal settingwhen using the generator as a stand-by power supply.Procedure 1. Before putting using the AUTO mode,perform a check of the auto start-upcircuit. To do so:a. Attach a short jumper wire (a)(minimum 16-gauge insulated)between the two terminals on theremote run terminal block. Thejumper wire applies a ground to theECM to complete the start circuit.b. Set the genset controller powerswitch (b) to the ON position.c. Press the AUTO mode button (c).d. Wait for the engine to crank, start,and run. If the engine cranks, the remote start circuit is functioning.e. Press the Stop/Reset “O” button (d) to stop the engine.f. Remove the jumper wire from the remote run terminals after testing iscomplete.This procedure continues on the next page.wc_gr011501cdbCAUTIONPossibility of accidental equipment start-up. If the contacts on any remote switchlinked to the generator are closed, the generator could start unexpectedly when theAUTO mode button is pressed.► Before pressing the AUTO mode button, verify that the contacts on any remoteswitch linked to the generator are OPEN.20A20A50A50A0 0 5 6 3 2AUSAUSAPAGADOAPAGADOARRETARRETOFFOFFREMOTE STARTREMOTE STARTFERNSTARTFERNSTARTARRANQUE REMOTOARRANQUE REMOTODEMARRAGE ADEMARRAGE ADISTANCEDISTANCESTART / LAUFENSTART / LAUFENARRANQUE / MARCHAARRANQUE / MARCHADEMARRER / MARCHEDEMARRER / MARCHESTART / RUNSTART / RUNawc_gr010206