wc_tx003229gb_FM10.fm80Mobile GeneratorWorking with Basler Controller8.10 Changing the Low Fuel Pre-Alarm SettingRequirements Machine stopped Start switch in REMOTE STARTNote: Internal programming of the genset controller, or closed connections to aremote start switch, may cause the machine to start unexpectedly. Be prepared forthe engine to start even with the engine start switch in the REMOTE STARTposition.Background The low fuel pre-alarm setting may be changed if desired. The value shown by thegenset controller is the percentage of fuel remaining in the fuel tank. The rangeallowed by the genset controller is 10–100.Procedure Perform the procedure below to change the low fuel pre-alarm setting.1. Press the right arrow button (1) to access the MAIN MENU.2. Using the up/down arrow buttons (2, 3) highlight SETTINGS. Then, press theright arrow button.3. Highlight ALARM CONFIGURATION. Then, press the right arrow button.4. Highlight PRE-ALARMS. Then, press the right arrow button.5. Highlight the LOW FUEL LEVEL. Then, press the right arrow button.6. Highlight the THRESHOLD. Then, press the check mark button (5).7. If you are not logged in, enter the password “OP”. Press the check mark button.This procedure continues on the next page.