n If the 10A for the power section supply is no longer sufficient, you may use the powermodule from VIPA with the order number 007-1AB00. So you have also the possibilityto define isolated groups.n The power module with the order number 007-1AB10 is to be used if the 3A for theelectronic power supply at the backplane bus is no longer sufficient. Additionally youget an isolated group for the DC 24V power section supply with max. 4A.n By placing the power module 007-1AB10 at the following backplane bus modulesmay be placed with a sum current of max. 2A. Afterwards a power module is to beplaced again. To secure the power supply, the power modules may be mixed used.(1) DC 24V for power section supply I/O area (max. 10A)(2) DC 24V for electronic power supply bus coupler and I/O area(3) DC 24V for power section supply I/O area (max. 4A)(4) DC 24V for electronic power supply I/O areaDeployment of the powermodulesPower module 007-1AB00Power module 007-1AB10VIPA System SLIOBasics and mountingWiring > Wiring power modulesHB300 | IM | 053-1EC00 | en | 16-4924