For wires with a core cross-section of 0.08mm2 up to 1.5mm2.Pos. Function Type Description1 --- --- not connected2 DC 24V I DC 24V for power section supply3 0V I GND for power section supply4 Sys DC 24V I DC 24V for electronic section supply5 --- --- not connected6 DC 24V I DC 24V for power section supply7 0V I GND for power section supply8 Sys 0V I GND for electronic section supplyI: Input8pin RJ45 jacks:n An EtherCAT network always consists of a master and an various number ofEtherCAT salves (coupler).n Each EtherCAT slave has an "IN" and "OUT" RJ45 jack. The arriving EtherCAT cablefrom the direction of the master is to be connected to the "IN" (Port 0) jack. The"OUT" (Port 1) jack is to be connected to the succeeding EtherCAT station. With therespective last EtherCAT station the "OUT" jack remains free.n EtherCAT uses Ethernet as transfer medium. Standard CAT5 cables are used. Heredistances of about 100m between 2 stations are possible.n Only EtherCAT components may be used in an EtherCAT network. For topologies,which depart from the line structure, the corresponding EtherCAT components arenecessary.n Hubs may not be used.3.2.2 LEDsPWR IO PWR PF Descriptiongreen green red● X ○ Power section supply OK● ● ○ Electronic section supply OKX X ● Fuse electronic section supply defectiveon: ● | off: ○ | not relevant: XPM - Power moduleInterface for EtherCATcommunicationLEDs power moduleVIPA System SLIO Hardware descriptionStructure > LEDsHB300 | IM | 053-1EC00 | en | 16-49 37