Actual signals and parameters 183Actual signalsActual signalsNo. Name/Value Description FbEq01 OPERATINGDATA Basic signals for monitoring the drive (read-only)0101 SPEED & DIR Calculated motor speed in rpm. A negative value indicatesreverse direction.1 = 1 rpm0102 SPEED Calculated motor speed in rpm 1 = 1 rpm0103 OUTPUTFREQCalculated drive output frequency in Hz. (Shown by defaulton the panel Output mode display.)1 = 0.1 Hz0104 CURRENT Measured motor current in A. (Shown by default on thepanel Output mode display.)1 = 0.1 A0105 TORQUE Calculated motor torque as a percentage of the motornominal torque1 = 0.1%0106 POWER Measured motor power in kW 1 = 0.1kW0107 DC BUSVOLTAGEMeasured intermediate circuit voltage in V DC 1 = 1 V0109 OUTPUTVOLTAGECalculated motor voltage in V AC 1 = 1 V0110 DRIVE TEMP Measured IGBT temperature in °C 1 = 0.1 °C0111 EXTERNALREF 1External reference REF1 in rpm or Hz. Unit depends onparameter 9904 MOTOR CTRL MODE setting.1 = 0.1 Hz/ 1 rpm0112 EXTERNALREF 2External reference REF2 as a percentage. Depending onthe use, 100% equals the maximum motor speed, nominalmotor torque, or maximum process reference.1 = 0.1%0113 CTRLLOCATIONActive control location. (0) LOCAL; (1) EXT1; (2) EXT2. Seesection Local control vs. external control on page 126.1 = 10114 RUN TIME (R) Elapsed drive running time counter (hours). Runs when thedrive is modulating. The counter can be reset by pressingthe UP and DOWN keys simultaneously when the controlpanel is in the Parameter mode.1 = 1 h0115 KWHCOUNTER (R)kWh counter. The counter value is accumulated till itreaches 65535 after which the counter rolls over and startsagain from 0. The counter can be reset by pressing UP andDOWN keys simultaneously when the control panel is in theParameter mode.1 = 1 kWh0120 AI 1 Relative value of analog input AI1 as a percentage 1 = 0.1%0121 AI 2 Relative value of analog input AI2 as a percentage 1 = 0.1%0124 AO 1 Value of analog output AO in mA 1 = 0.1mA0126 PID 1 OUTPUT Output value of the process PID1 controller as a percentage 1 = 0.1%0127 PID 2 OUTPUT Output value of the PID2 controller as a percentage 1 = 0.1%