290 Actual signals and parameters5205 PARITYERRORSNumber of characters with a parity error received from theModbus link. If the number is high, check that the paritysettings of the devices connected on the bus are the same.Note: High electromagnetic noise levels generate errors.00…65535 Number of characters 1 = 15206 FRAMEERRORS Number of characters with a framing error received by theModbus link. If the number is high, check that thecommunication speed settings of the devices connected onthe bus are the same.Note: High electromagnetic noise levels generate errors.00…65535 Number of characters 1 = 15207 BUFFEROVERRUNSNumber of characters which overflow the buffer, ie, numberof characters which exceed the maximum message length,128 bytes.00…65535 Number of characters 1 = 15208 CRC ERRORS Number of messages with an CRC (cyclic redundancycheck) error received by the drive. If the number is high,check CRC calculation for possible errors.Note: High electromagnetic noise levels generate errors.00…65535 Number of messages 1 = 153 EFB PROTOCOL Embedded fieldbus link settings. See chapter Fieldbuscontrol with embedded fieldbus on page 313.5302 EFB STATIONIDDefines the address of the device. Two units with the sameaddress are not allowed on-line.10…247 Address 1 = 15303 EFB BAUDRATEDefines the transfer rate of the link. 9.6 kb/s1.2 kb/s 1.2 kbit/s 1 =0.1 kbit/s2.4 kb/s 2.4 kbit/s4.8 kb/s 4.8 kbit/s9.6 kb/s 9.6 kbit/s19.2 kb/s 19.2 kbit/s38.4 kb/s 38.4 kbit/s57.6 kb/s 57.6 kbit/s115.2 kb/s 115.2 kbit/s5304 EFB PARITY Defines the use of parity and stop bit(s) and the data length.The same setting must be used in all on-line stations.8 NONE 18 NONE 1 No parity bit, one stop bit, 8 data bits 08 NONE 2 No parity bit, two stop bits, 8 data bits 1All parametersNo. Name/Value Description Def/FbEq