Parameters 2753535 Motor thermalprotectionMotor thermal protection settings such as temperaturemeasurement configuration, load curve definition and motorfan control configuration.See also section Motor thermal protection (page 80).35.01 Motor estimatedtemperatureDisplays the motor temperature as estimated by the internalmotor thermal protection model (see parameters35.50…35.55). The unit is selected by parameter 96.16 UnitselectionThis parameter is read-only.--60 … 1000°C or °FEstimated motor temperature. 1 = 1°35.02 Measuredtemperature 1Displays the temperature received through the sourcedefined by parameter 35.11 Temperature 1 source. The unit isselected by parameter 96.16 Unit selection.Note: With a PTC sensor, the unit is ohms.This parameter is read-only.--60 … 5000 °C,-76 … 9032 °F,0 ohm or[35.12] ohmMeasured temperature 1. 1 = 1 unit35.03 Measuredtemperature 2Displays the temperature received through the sourcedefined by parameter 35.21 Temperature 2 source. The unitis selected by parameter 96.16 Unit selection.Note: With a PTC sensor, the unit is ohms.This parameter is read-only.--60 … 5000 °C,-76 … 9032 °F,0 ohm or[35.22] ohmMeasured temperature 2. 1 = 1 unitNo. Name/Value Description Def/FbEq16