388 Parameters94.30 Reactive powerreferenceDisplays the reactive power reference sent to the supply unit.This parameter is read-only.--3276.8 … 3276.7kvarReactive power reference sent to the supply unit. 10 = 1 kvar94.31 Reactive power refsourceSelects the source of the reactive power reference to be sentto the supply unit.User refZero None. 0User ref 94.32 User reactive power reference. 1Other Source selection (see Terms and abbreviations on page 112). -94.32 User reactive powerreferenceDefines the reactive power reference for the supply unit when94.31 Reactive power ref source is set to User ref.0.0 kvar-3276.8 … 3276.7kvarUser reactive power reference. 10 = 1 kvar9595 HW configuration Various hardware-related settings.95.01 Supply voltage Selects the supply voltage range. This parameter is used bythe drive to determine the nominal voltage of the supplynetwork. The parameter also affects the current ratings andthe DC voltage control functions (trip and brake chopperactivation limits) of the drive.WARNING! An incorrect setting may cause the motorto rush uncontrollably, or the brake chopper or resistorto overload.Note: The selections shown depend on the hardware of thedrive. If only one voltage range is valid for the drive inquestion, it is selected by default.-Not given No voltage range selected. The drive will not start modulatingbefore a range is selected.0208…240 V 208…240 V 1380…415 V 380…415 V 2440…480 V 440…480 V 3500 V 500 V 4525…600 V 525…600 V 5660…690 V 660…690 V 695.02 Adaptive voltagelimitsEnables adaptive voltage limits.Adaptive voltage limits can be used if, for example, an IGBTsupply unit is used to raise the DC voltage level. The limitsare calculated based on the measured DC voltage at the endof the pre-charging sequence.This function is also useful if the AC supply voltage to thedrive is high, as the warning levels are raised accordingly.DisableDisable Adaptive voltage limits disabled. 0Enable Adaptive voltage limits enabled. 195.04 Control boardsupplySpecifies how the control unit of the drive is powered. Internal 24V;External 24V(95.20 b4)Internal 24V The drive control unit is powered from the drive power unit itis connected to.0External 24V The drive control unit is powered from an external powersupply.1No. Name/Value Description Def/FbEq16