Parameters and firmware blocks103Group 10 START/STOPSettings for• selecting start/stop/direction signal sources for external control locations EXT1and EXT2• selecting sources for external fault reset, run enable and start enable signals• selecting sources for emergency stop (OFF1 and OFF3)• selecting source for jogging function activation signal• enabling the start inhibit function.See also section Jogging on page 46.1010 START/STOPFirmware block:DRIVE LOGIC(10)This block• selects the sources for the start/stop/direction signals for externalcontrol locations EXT1 and EXT2• selects the sources for externalfault reset, run enable and startenable signals• selects the sources for emergencystop (OFF1 and OFF3)• selects the source for joggingactivation signal• enables the start inhibit function.DRIVE LOGIC 21TLF10 2 msec (3)10.01 EXT1 START FUNC[ In1 ]< 10.02 EXT1 START IN1[ DI STATUS.0 ](2 / 2.01.DI1)< 10.03 EXT1 START IN2[ FALSE ]10.04 EXT2 START FUNC[ In1 ]< 10.05 EXT2 START IN1[ DI STATUS.0 ](2 / 2.01.DI1)< 10.06 EXT2 START IN2[ FALSE ]< 10.07 JOG1 START[ FALSE ]< 10.08 FAULT RESET SEL[ DI STATUS.2 ](2 / 2.01.DI3)< 10.09 RUN ENABLE[ TRUE ]< 10.10 EM STOP OFF3[ TRUE ]< 10.11 EM STOP OFF1[ TRUE ]10.12 START INHIBIT[ Disabled ]< 10.13 FB CW USED[ FBA MAIN CW ](4 / 2.12)< 10.14 JOG2 START[ FALSE ]< 10.15 JOG ENABLE[ FALSE ]< 10.16 D2D CW USED[ D2D MAIN CW ](4 / 2.17)< 10.17 START ENABLE[ TRUE ]2.18 D2D FOLLOWER CW6.01 STATUS WORD 16.02 STATUS WORD 26.03 SPEED CTRL STAT6.05 LIMIT WORD 16.07 TORQ LIM STATUS6.09 POS CTRL STATUS6.10 POS CTRL STATUS26.11 POS CORR STATUS