Table 68:GOOSERCV_INTL Output signalsName Type DescriptionOP BOOLEAN Position open output signalCL BOOLEAN Position closed output signalOK BOOLEAN Position OK output signalVALID BOOLEAN Output signal3.12.6 GOOSERCV_CMV function block3.12.6.1 Function blockGUID-4C3F3A1A-F5D1-42E1-840F-6106C58CB380 V1 ENFigure 35: Function block3.12.6.2 FunctionalityThe GOOSERCV_CMV function is used to connect GOOSE measured valueinputs to the application. The MAG_IN (amplitude) and ANG_IN (angle) inputsare defined in the GOOSE configuration (PCM600).The MAG output passes the received GOOSE (amplitude) value for theapplication. Default value (0) is used if VALID output indicates invalid status.The ANG output passes the received GOOSE (angle) value for the application.Default value (0) is used if VALID output indicates invalid status.3.12.6.3 SignalsTable 69:GOOSERCV_CMV Input signalsName Type Default DescriptionMAG_IN FLOAT32 0 Input signal(amplitude)ANG_IN FLOAT32 0 Input signal (angle)Table 70:GOOSERCV_CMV Output signalsName Type DescriptionMAG FLOAT32 Output signal (amplitude)ANG FLOAT32 Output signal (angle)VALID BOOLEAN Output signal1YHT530004D05 D Section 3Basic functions615 series 101Technical Manual