4.1.3.9 SettingsTable 203:DPHLPDOC Group settingsParameter Values (Range) Unit Step Default DescriptionStart value 0.05...5.00 xIn 0.01 0.05 Start valueStart value Mult 0.8...10.0 0.1 1.0 Multiplier for scaling the start valueTime multiplier 0.05...15.00 0.01 1.00 Time multiplier in IEC/ANSI IDMT curvesOperate delay time 40...200000 ms 10 40 Operate delay timeOperating curve type 1=ANSI Ext. inv.2=ANSI Very inv.3=ANSI Norm. inv.4=ANSI Mod. inv.5=ANSI Def. Time6=L.T.E. inv.7=L.T.V. inv.8=L.T. inv.9=IEC Norm. inv.10=IEC Very inv.11=IEC inv.12=IEC Ext. inv.13=IEC S.T. inv.14=IEC L.T. inv.15=IEC Def. Time17=Programmable18=RI type19=RD type15=IEC Def. Time Selection of time delay curve typeType of reset curve 1=Immediate2=Def time reset3=Inverse reset1=Immediate Selection of reset curve typeVoltage Mem time 0...3000 ms 1 40 Voltage memory timeDirectional mode 1=Non-directional2=Forward3=Reverse2=Forward Directional modeCharacteristic angle -179...180 deg 1 60 Characteristic angleMax forward angle 0...90 deg 1 80 Maximum phase angle in forwarddirectionMax reverse angle 0...90 deg 1 80 Maximum phase angle in reversedirectionMin forward angle 0...90 deg 1 80 Minimum phase angle in forward directionMin reverse angle 0...90 deg 1 80 Minimum phase angle in reverse directionPol quantity -2=Pos. seq. volt.1=Self pol4=Neg. seq. volt.5=Cross pol5=Cross pol Reference quantity used to determinefault direction1YHT530004D05 D Section 4Protection functions615 series 195Technical Manual