Table 397:PHPTUV Non group settingsParameter Values (Range) Unit Step Default DescriptionOperation 1=on5=off1=on Operation Off / OnNum of start phases 1=1 out of 32=2 out of 33=3 out of 31=1 out of 3 Number of phases required for operateactivationMinimum operate time 60...60000 ms 1 60 Minimum operate time for IDMT curvesReset delay time 0...60000 ms 1 20 Reset delay timeCurve parameter A 0.005...200.000 1.000 Parameter A for customer programmablecurveCurve parameter B 0.50...100.00 1.00 Parameter B for customer programmablecurveCurve parameter C 0.0...1.0 0.0 Parameter C for customerprogrammable curveCurve parameter D 0.000...60.000 0.000 Parameter D for customerprogrammable curveCurve parameter E 0.000...3.000 1.000 Parameter E for customer programmablecurveCurve Sat Relative 0.0...3.0 0.1 2.0 Tuning parameter to avoid curvediscontinuitiesVoltage block value 0.05...1.00 xUn 0.01 0.20 Low level blocking for undervoltage modeEnable block value 0=False1=True1=True Enable internal blockingVoltage selection 1=phase-to-earth2=phase-to-phase2=phase-to-phase Parameter to select phase or phase-to-phase voltagesRelative hysteresis 1.0...5.0 % 0.1 4.0 Relative hysteresis for operation4.5.2.9 Monitored dataTable 398:PHPTUV Monitored dataName Type Values (Range) Unit DescriptionSTART_DUR FLOAT32 0.00...100.00 % Ratio of start time /operate timePHPTUV Enum 1=on2=blocked3=test4=test/blocked5=offStatusSection 4 1YHT530004D05 DProtection functions480 615 seriesTechnical Manual