Fault indication Fault code Additional informationInternal FaultConf. error,X11064 Card in slot X110 is wrong type, ismissing or does not belong to the originalcomposition.Internal FaultConf. error,X12065 Card in slot X120 is wrong type, ismissing or does not belong to the originalcomposition.Internal FaultConf.error,X13066 Card in slot X130 is wrong type, ismissing or does not belong to the originalcomposition.Internal FaultCard error,X00072 Card in slot X000 is faulty.Internal FaultCard error,X10073 Card in slot X100 is faulty.Internal FaultCard error,X11074 Card in slot X110 is faulty.Internal FaultCard error,X12075 Card in slot X120 is faulty.Internal FaultCard error,X13076 Card in slot X130 is faulty.Internal FaultLHMI module79 LHMI module is faulty. The faultindication may not be seen on the LHMIduring the fault.Internal FaultRAM error80 Error in the RAM memory on the CPUcard.Internal FaultROM error81 Error in the ROM memory on the CPUcard.Internal FaultEEPROM error82 Error in the EEPROM memory on theCPU card.Internal FaultFPGA error83 Error in the FPGA on the CPU card.Internal FaultRTC error84 Error in the RTC on the CPU card.Internal FaultRTD card error,X13096 RTD card located in slot X130 may havepermanent fault. Temporary error hasoccurred too many times within a shorttime.For further information on internal fault indications, see the operation manual.3.2.2 WarningsIn case of a warning, the IED continues to operate except for those protectionfunctions possibly affected by the fault, and the green Ready LED remains lit asduring normal operation.Warnings are indicated with the text Warning additionally provided with thename of the warning, a numeric code and the date and time on the LHMI. Thewarning indication message can be manually cleared.1YHT530004D05 D Section 3Basic functions615 series 61Technical Manual