Name Type DescriptionPARALLEL BOOLEAN Parallel or single operationAUTO BOOLEAN Auto/Manual indicationTIMER_ON BOOLEAN Timer onBLKD_I_LOD BOOLEAN Indication of over current blockingBLKD_U_UN BOOLEAN Indication of under voltage blockingRNBK_U_OV BOOLEAN Indication of raise voltage runbackBLKD_I_CIR BOOLEAN Indication of high circulating current blockingBLKD_LTCBLK BOOLEAN Indication of external blocking9.5.17 SettingsTable 638:OLATCC Group settingsParameter Values (Range) Unit Step Default DescriptionAuto parallel mode 2=Auto master3=Auto follower5=NRP7=MCC2=Auto master Parallel mode selectionBand center voltage 0.000...2.000 xUn 0.001 1.000 Band center voltage UsLine drop V Ris 0.0...25.0 % 0.1 0.0 Resistive line-drop compensation factorLine drop V React 0.0...25.0 % 0.1 0.0 Reactive line-drop compensation factorBand reduction 0.00...9.00 %Un 0.01 0.00 Step size for reduce set voltage (RSV)Stability factor 0.0...70.0 % 0.1 0.0 Stability factor in parallel operationLoad phase angle -89...89 deg 1 0 Load phase-shift, used only with thenegative reactance principleControl delay time 1 1000...300000 ms 100 60000 Control delay time for the first controlpulseControl delay time 2 1000...300000 ms 100 30000 Control delay time for the followingcontrol pulsesTable 639:OLATCC Non group settingsParameter Values (Range) Unit Step Default DescriptionOperation 1=on5=off1=on Operation Off / OnOperation mode 1=Manual2=Auto single3=Auto parallel4=Input control4=Input control The operation modeCustom Man blocking 1=Custom disabled2=OC3=UV4=OC, UV5=EXT6=OC, EXT7=UV, EXT8=OC, UV, EXT2=OC Customized manual blockingTable continues on next page1YHT530004D05 D Section 9Control functions615 series 759Technical Manual