Name Type Default DescriptionPRES_ALM_IN BOOLEAN 0=False Binary pressure alarm inputPRES_LO_IN BOOLEAN 0=False Binary pressure input for lockout indicationSPR_CHR_ST BOOLEAN 0=False CB spring charging started inputSPR_CHR BOOLEAN 0=False CB spring charged inputRST_IPOW BOOLEAN 0=False Reset accumulation energyRST_CB_WEAR BOOLEAN 0=False Reset input for CB remaining life and operationcounterRST_TRV_T BOOLEAN 0=False Reset input for CB closing and opening travel timesRST_SPR_T BOOLEAN 0=False Reset input for the charging time of the CB springTable 526:SSCBR Output signalsName Type DescriptionTRV_T_OP_ALM BOOLEAN CB open travel time exceeded set valueTRV_T_CL_ALM BOOLEAN CB close travel time exceeded set valueSPR_CHR_ALM BOOLEAN Spring charging time has crossed the set valueOPR_ALM BOOLEAN Number of CB operations exceeds alarm limitOPR_LO BOOLEAN Number of CB operations exceeds lockout limitIPOW_ALM BOOLEAN Accumulated currents power (Iyt),exceeded alarmlimitIPOW_LO BOOLEAN Accumulated currents power (Iyt),exceededlockout limitCB_LIFE_ALM BOOLEAN Remaining life of CB exceeded alarm limitMON_ALM BOOLEAN CB 'not operated for long time' alarmPRES_ALM BOOLEAN Pressure below alarm levelPRES_LO BOOLEAN Pressure below lockout levelOPENPOS BOOLEAN CB is in open positionINVALIDPOS BOOLEAN CB is in invalid position (not positively open orclosed)CLOSEPOS BOOLEAN CB is in closed position7.1.7 SettingsTable 527:SSCBR Non group settingsParameter Values (Range) Unit Step Default DescriptionOperation 1=on5=off1=on Operation Off / OnAcc stop current 5.00...500.00 A 0.01 10.00 RMS current setting below which engyacm stopsOpen alarm time 0...200 ms 1 40 Alarm level setting for open travel time inmsClose alarm time 0...200 ms 1 40 Alarm level Setting for close travel timein msTable continues on next pageSection 7 1YHT530004D05 DCondition monitoring functions620 615 seriesTechnical Manual