Table 52:Settings for X130 (RTD) analog input limit value supervisionFunction Settings for limit value supervisionX130 (RTD) analog input Out of range Value maximumHigh-high limit Val high high limitHigh limit Val high limitLow limit Val low limitLow-low limit Val low low limitOut of range Value minimumWhen the measured value exceeds either the Value maximum setting or the Valueminimum setting, the corresponding quality is set to out of range and a maximumor minimum value is shown when the measured value exceeds the addedhysteresis, respectively. The hysteresis is added to the extreme value of the rangelimit to allow the measurement slightly to exceed the limit value before it isconsidered as out of range.3.11.2.8 Deadband supervisionEach input has an independent deadband supervision. The deadband supervisionfunction reports the measured value according to integrated changes over a timeperiod.GUID-63CA9A0F-24D8-4BA8-A667-88632DF53284 V1 ENFigure 26: Integral deadband supervisionThe deadband value used in the integral calculation is configured with the Valuedeadband setting. The value represents the percentage of the difference betweenthe maximum and minimum limits in the units of 0.001 percent * seconds. Thereporting delay of the integral algorithms in seconds is calculated with the formula:t s Y( ) (= ×∆ ×Value maximum - Value minimum) deadband / 10001000%GUID-CC447162-C1B4-4E74-A253-828F388266EB V1 EN (Equation )Section 3 1YHT530004D05 DBasic functions90 615 seriesTechnical Manual