7.1.8 Monitored dataTable 528:SSCBR Monitored dataName Type Values (Range) Unit DescriptionT_TRV_OP FLOAT32 0...60000 ms Travel time of the CBduring opening operationT_TRV_CL FLOAT32 0...60000 ms Travel time of the CBduring closing operationT_SPR_CHR FLOAT32 0.00...99.99 s The charging time of theCB springNO_OPR INT32 0...99999 Number of CB operationcycleINA_DAYS INT32 0...9999 The number of days CBhas been inactiveCB_LIFE_A INT32 -9999...9999 CB Remaining life phaseACB_LIFE_B INT32 -9999...9999 CB Remaining life phaseBCB_LIFE_C INT32 -9999...9999 CB Remaining life phaseCIPOW_A FLOAT32 0.000...30000.000Accumulated currentspower (Iyt), phase AIPOW_B FLOAT32 0.000...30000.000Accumulated currentspower (Iyt), phase BIPOW_C FLOAT32 0.000...30000.000Accumulated currentspower (Iyt), phase CSSCBR Enum 1=on2=blocked3=test4=test/blocked5=offStatus7.1.9 Technical dataTable 529:SSCBR Technical dataCharacteristic ValueCurrent measuring accuracy ±1.5% or ±0.002 x In(at currents in the range of 0.1…10 x In)±5.0%(at currents in the range of 10…40 x In)Operate time accuracy ±1.0% of the set value or ±20 msTravelling time measurement +10 ms / -0 msSection 7 1YHT530004D05 DCondition monitoring functions622 615 seriesTechnical Manual