9.3.7 SettingsTable 613:Synchronism and energizing check (SECRSYN) main settingsParameter Values (Range) Unit Step Default DescriptionLive dead mode -1=Off1=Both Dead2=Live L, Dead B3=Dead L, Live B4=Dead Bus, L Any5=Dead L, Bus Any6=One Live, Dead7=Not Both Live1=Both Dead Energizing checkmodeDifference voltage 0.01...0.50 xUn 0.01 0.05 Maximum voltagedifference limitDifference frequency 0.001...0.100 xFn 0.001 0.001 Maximum frequencydifference limitDifference angle 5...90 deg 1 5 Maximum angledifference limitSynchrocheck mode 1=Off2=Synchronous3=Asynchronous2=Synchronous Synchrocheckoperation modeControl mode 1=Continuous2=Command1=Continuous Selection of thesynchrocheckcommand orcontinuous controlmodeDead line value 0.1...0.8 xUn 0.1 0.2 Voltage low-limit linefor energizing checkLive line value 0.2...1.0 xUn 0.1 0.5 Voltage high-limitline for energizingcheckClose pulse 200...60000 ms 10 200 Breaker-closingpulse durationMax energizing V 0.50...1.15 xUn 0.01 1.05 Maximum voltagefor energizingPhase shift -180...180 deg 1 180 Correction of phasedifference betweenmeasured U_BUSand U_LINEMinimum Syn time 0...60000 ms 10 0 Minimum time toaccept synchronizingMaximum Syn time 100...6000000 ms 10 2000 Maximum time toaccept synchronizingEnergizing time 100...60000 ms 10 100 Time delay forenergizing checkClosing time of CB 40...250 ms 10 60 Closing time of thebreakerSection 9 1YHT530004D05 DControl functions690 615 seriesTechnical Manual