and the bus voltage is above 80% of the bus base voltage UBase, according to thesetting GblBaseSelBus.• DBLL, Dead Bus Live Line, the bus voltage is below 40% of the bus base voltageUBase, according to the setting GblBaseSelBus about the Global Base Value group,and the line voltage is above 80% of the line base voltage UBase, according to thesetting GblBaseSelLine.• Both, energizing can be done in both directions, DLLB or DBLL.ManEnergDBDLIf the parameter is set to Enabled, manual closing is enabled when line voltage is below40% of the line base voltage UBase, according to the setting GblBaseSelLine about theGlobal Base Value group, and when bus voltage is below 40% of the bus base voltageUBase, according to the setting GblBaseSelBus and also ManEnerg is set to DLLB, DBLLor Both.tAutoEnerg and tManEnergThe purpose of the timer delay settings, tAutoEnerg and tManEnerg, is to ensure that thedead side remains de-energized and that the condition is not due to a temporaryinterference. Should the conditions not persist for the specified time, the delay timer isreset and the procedure is restarted when the conditions are fulfilled again. Circuit breakerclosing is thus not permitted until the energizing condition has remained constantthroughout the set delay setting time.11.2 Autorecloser for 3-phase operation SMBRREC (79)11.2.1 IdentificationFunction Description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberAutorecloser for 3-phase operation SMBRRECO->ISYMBOL-L V1 EN7911.2.2 ApplicationAutomatic reclosing is a well-established method for the restoration of service in a powersystem after a transient line fault. The majority of line faults are flashover arcs, which are1MRK 506 334-UUS A Section 11Control303Application manual