1. Set the primary and secondary values for current transformer input 1.1.1. Set CT_WyePoint1 to ToObject(The CT secondary is grounded towards the protected line)1.2. Set CTSec1 to 1 A(The rated secondary current of the CT)1.3. Set CTPrim1 to 1000 A(The rated primary current of the CT)2. Set the same values for the current inputs 2 and 3.Current input 4 can be used for residual current input from parallelline. This current is normally used for compensation of the faultlocator function influence from the parallel line. In this applicationthe input is not used.Current input 5 can be used for connection of a current transformerdedicated for residual current protection. A special currenttransformer with a ratio adapted to achieve high sensitivity of theprotection is used. In this application the input is not used.3. Set the primary and secondary values for voltage transformer inputs 6.3.1. Set VTSec6 to 110 V(The rated secondary voltage of the VT, given as phase-phase voltage)3.2. Set VTPrim6 to 143 kV(The rated secondary voltage of the VT, given as phase-phase voltage)4. Set the same values for inputs 7 and 8.Voltage inputs 9 and 10 can be used for busbar voltage measurementto enable the synchronism check function. In this application theinputs are not used.3.1.2 Calculating settings for Global base values for setting functionGBASVALEach function uses primary base values for reference of settings. The base vaules aredefined in Global base values for settings function. It is possible to include up to six Globalbase values for settings functions. Only one Global base values for settings functions is1MRK 506 334-UUS A Section 3REL650 setting examples43Application manual