The operation from local HMI is from select or indication buttons (32 positions). Typicalapplications are: Select operating modes for e.g. Auto reclose, Energizing check, Groundfault protection (IN,UN). The output integer can be connected to an Integer to Binaryfunction block to give the position as a boolean for use in the configuration.11.6.3 Setting guidelinesThe following settings are available for the Logic rotating switch for function selectionand LHMI presentation (SLGGIO) function:Operation: Sets the operation of the function Enabled or Disabled.NrPos: Sets the number of positions in the switch (max. 32). This setting influence thebehavior of the switch when changes from the last to the first position.OutType: Steady or Pulsed.tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).tDelay: The delay between the UP or DOWN activation signal positive front and theoutput activation.StopAtExtremes: Sets the behavior of the switch at the end positions – if set to Disabled,when pressing UP while on first position, the switch will jump to the last position; whenpressing DOWN at the last position, the switch will jump to the first position; when set toEnabled, no jump will be allowed.11.7 Selector mini switch VSGGIO11.7.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberSelector mini switch VSGGIO - -11.7.2 ApplicationSelector mini switch (VSGGIO) function is a multipurpose function used in theconfiguration tool in PCM600 for a variety of applications, as a general purpose switch.VSGGIO can be used for both acquiring an external switch position (through the IPOS1and the IPOS2 inputs) and represent it through the single line diagram symbols (or use itin the configuration through the outputs POS1 and POS2) as well as, a command functionSection 11 1MRK 506 334-UUS AControl386Application manual