The following trip parameters can be set to regulate tripping.ProgramSet the required tripping scheme depending on value selected 3 phase or 1p/3p.OperationSets the mode of operation. Disabled switches the tripping off. The normal selection isEnabled.TripLockoutSets the scheme for lock-out. Disabled only activates lock-out output. Enabled activatesthe lock-out output and latching output contacts. The normal selection is Disabled.AutoLockSets the scheme for lock-out. Disabled only activates lock-out through the inputSETLKOUT. Enabled also allows activation from trip function itself and activates thelockout output. The normal selection is Disabled.tTripMinSets the required minimum duration of the trip pulse. It should be set to ensure that thebreaker is tripped and if a signal is used to initiate the Breaker failure protection phasesegregated activation and output CSPRBRF (50BF) function longer than the back-up triptimer in CSPRBRF (50BF). Normal setting is 0.150s.13.3 Trip matrix logic TMAGGIO13.3.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberTrip matrix logic TMAGGIO - -13.3.2 ApplicationThe 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to route tripsignals and other logical output signals to the tripping logics SMPPTRC and SPTPTRCor to different output contacts on the IED.Section 13 1MRK 506 334-UUS ALogic418Application manual