CHAPTER 4Using the Gateway190Conversion settingsFigure 207. Sensor type - Conversion settings - Digital• Sensor table - if you want to use a non-linear sensor, selectone of the sensor tables already defined in the menu item“Sensor Tables” for conversion/linearization; if you intend touse a linear sensor, select “none”;Figure 208. Sensor type - Conversion settings - Sensor table - DigitalNote: If a sensor table is entered for a non-linear sensor, the fol-lowing entries for Linear input value refer to the output val-ues of the linearization table and not to the voltagemeasured on the analog pin!• Linear input value - entry of the minimum and maximum valueof the range within which the sensor delivers measurements;Note: Due to its linear characteristic, a linear sensor is by defaultexactly defined by only two input values, the minimum andthe maximum. The range for digital sensors is 0 - 1 Units.• Linear output value - entry of the minimum and maximumvalue of the linear output range which has to correspond tothe linear input value range, in the engineering units whichhave been selected;• Verifier - entry of the minimum and maximum value withinwhich valid sensor measurement results can be expected. If