C-7AMI Operation CommandsAlarm/trap reset threshold Shows the temperature in oC at which an overtem-perature alarm is reset. For example, if the user setsthe reset and trip thresholds to 50 oC and 60 oC,respectively, then the alarm will trip at 60 oC, and itwill be reset when the temperature drops back downto 50 oC.Alarm/trap trip threshold Shows the temperature in oC at which an overtem-perature alarm is tripped. For example, if the usersets the reset and trip thresholds to 50 oC and 60 oC,respectively, then the alarm will trip at 60 oC, and itwill be reset when the temperature drops back downto 50 oC.C.2.4 Configuring the Switch Fabric Temperature ThresholdsThis command allows the user to set the thresholds at which a temperaturealarm will be tripped and then later reset on an SFCS-1000. Any temperaturecan cause the switch to display a state of normal or overTemp, depending onthe trip and reset thresholds set by the user. For example, a temperature of 55oC would show a state of normal if the trip threshold was 60 oC and theswitch fabric temperature never reached 60 degrees, but it would show a stateof overTemp if the switch fabric temperature had reached 60 oC, and thenhad dropped to 55 oC, but had not yet reached a reset threshold set at 50 oC.Enter the following parameters:localhost::operation environment fabric> temperature reset threshold Indicates the temperature in oC at which an overtem-perature alarm is reset. The default is 60 oC.trip threshold Indicates the temperature in oC at which an overtem-perature alarm is tripped. The default is 65 oC.