VLT ® 2800 SeriesAll about VLT2800VLT 2803-2875 EmissionIndustrial environment Residential, commercial and light industryEN 55011 class 1A EN 55011 class 1BSetup Cable-borne150 kHz- 30 MHzRadiated30 MHz - 1 GHzCable-borne150 kHz - 30 MHzRadiated30 MHz - 1 GHz3 x 480 V version with1A RFI filterYes25 mscreened/armouredYes25 m screened/ar-mouredNo No3 x 480 V version with1A RFI filter (R5: For ITmains)Yes5 mscreened/armouredYes5 m screened/ar-mouredNo No1 x 200 V version with1A RFI filter 1.Yes40 mscreened/armouredYes40 m screened/ar-mouredYes15 m screened/ar-mouredNo3 x 200 V version with1A RFI filter (R4: For usewith RCD)Yes20 mscreened/armouredYes20 m screened/ar-mouredYes7 m screened/ar-mouredNo3 x 480 V version with1A+1B RFI filterYes50 mscreened/armouredYes50 m screened/ar-mouredYes25 m screened/ar-mouredNo1 x 200 V version with1A+1B RFI filter 1.Yes100 mscreened/armouredYes100 mscreened/armouredYes40 m screened/ar-mouredNoVLT 2880-2882 EmissionIndustrial environment Residential, commerce and light industryEN 55011 class 1A EN 55011 class 1BSetup Cable-borne150 kHz- 30 MHzRadiated30 MHz - 1 GHzCable-borne150 kHz - 30 MHzRadiated30 MHz - 1 GHz3 x 480 V version with1B RFI filterYes50 mYes50 mYes50 mNo1. For VLT 2822-2840 3 x 200-240 V the same valuesapply as for the 480 V version with 1A RFI filter.MG.28.E9.02 - VLT is a registered Danfoss trademark 137