VLT ® 2800 SeriesPNU#ParameterdescriptionFactory setting 4-setup Conv.indexDatatype302 Digital input, term. 18 Start Yes 0 5303 Digital input, term. 19 Reversing Yes 0 5304 Digital input, term. 27 Reset and coastinverseYes 0 5305 Digital input, term. 29 Jog Yes 0 5307 Digital input, term. 33 No function Yes 0 5308 Term. 53, analogue input voltage Reference Yes 0 5309 Term. 53, min scaling 0.0 V Yes -1 6310 Term. 53, max scaling 10.0 V Yes -1 6314 Term. 60, analogue input current No function Yes 0 5315 Term. 60, min scaling 0.0 mA Yes -4 6316 Term. 60, max scaling 20.0 mA Yes -4 6317 Time out 10 sec. Yes -1 5318 Function after timeout No function Yes 0 5319 Term. 42, analogue output 0-I MAX = 0-20 mA Yes 0 5323 Relay output Control ready Yes 0 5327 Pulse ref./FB 5000 Hz Yes 0 7341 Term. 46 digital output Control ready Yes 0 5342 Term. 46 Max. pulse output 5000 Hz Yes 0 6343 Precise stop function Normal ramp stop Yes 0 5344 Counter value 100000 pulses Yes 0 7349 Speed comp delay 10 ms Yes -3 64-Setup:’Yes’ means that the parameter can be programmedindividually in each of the four Setups, i.e. one singleparameter can have four different data values. ’No’means that the data value will be the same in all Setups.Conversion index:This number refers to a conversion figure to be usedwhen writing or reading via serial communicationwith a frequency converter.See Data character in Serial communicationin the Design Guide.Data type:Data type shows the type and length of the telegram.Data type Description3 Integer 164 Integer 325 Unsigned 86 Unsigned 167 Unsigned 329 Text stringMG.28.E9.02 - VLT is a registered Danfoss trademark156