VLT ® 2800 SeriesIntroduction to VLT2800This section makes it easier for you to specify andorder a VLT 2800.Choice of frequency converterThe frequency converter must be chosen on thebasis of the present motor current at maximumloading of the unit. The frequency converter’s ratedoutput current I INV. must be equal to or greater thanthe required motor current.Mains voltageVLT 2800 is available for two mains voltageranges: 200-240 V and 380-480 V.Select whether the frequency converter isconnected to a mains voltage of:- 1 x 220 - 240 V single-phase AC voltage- 3 x 200 - 240 V three-phase AC voltage- 3 x 380 - 480 V three-phase AC voltage1 x 220 - 240 Volt mains voltageTypical shaft outputP INV.Max. constant outputcurrent I INV.Max. constant output powerat 230 V S INV.Type [kW] [HP] [A] [kVA]2803 0.37 0.5 2.2 0.92805 0.55 0.75 3.2 1.32807 0.75 1.0 4.2 1.72811 1.1 1.5 6.0 2.42815 1.5 2.0 6.8 2.73 x 200 - 240 Volt mains voltageTypical shaft outputP INV.Max. constant outputcurrent I INV.Max. constant output powerat 230 V S INV.Type [kW] [HP] [A] [kVA]2803 0.37 0.5 2.2 0.92805 0.55 0.75 3.2 1.32807 0.75 1.0 4.2 1.72811 1.1 1.5 6.0 2.42815 1.5 2.0 6.8 2.72822 2.2 3.0 9.6 3.82840 3.7 5.0 16.0 6.4MG.28.E9.02 - VLT is a registered Danfoss trademark 9