Power Monitoring and Management295Using RACADMracadmconfig-gcfgServerPower-ocfgServerPowerCapWatts <powercapvaluein Watts>racadmconfig-gcfgServerPower-ocfgServerPowerCapBTUhr <powercapvaluein BTU/hr>racadmconfig-gcfgServerPower-ocfgServerPowerCapPercentcapvaluein%>racadmconfig-gcfgServerPower-ocfgServerPowerCapEnable=<1toenable,0to disable>NOTE:When setting the power budget threshold in BTU/hr, the conversion toWatts is rounded to the nearest integer. When reading the power budget thresholdback, the Watts to BTU/hr conversion is again rounded in this manner. As a result,the value written could be nominally different than the value read; for example, athreshold set to 600 BTU/hr will be read back as 601 BTU/hr.Viewing Power MonitoringUsing the Web InterfaceTo view the power monitoring data:1Log in to the iDRAC6 Web interface.2SelectPower Monitoringin the system tree. ThePower Monitoringpage displays.The information provided on thePower Monitoringpage is described below:Power Monitoring•Status:OKindicates that the power supply units are present andcommunicating with the server,Warningindicates that a warning alert wasissued, andSevereindicates a failure alert was issued.•Probe Name: System Board System Level. This description indicates theprobe is being monitored by its location in the system.•Reading: The current power consumption in Watts/BTU/hr.