eZV-440 Application GuideEdition 2.6Page 27 of 84Function Select this option if you are using a:SpcTemp+OccToggleButton_Space temperature sensor and the occupancy toggle pushbutton are wired into the same input.This can be a normally open contact wired in parallel or anormally closed contact wired in series with the temperaturesensor.When setting up a temperature sensor, majority of the cases would require you to selectTemp_10K3DegC or Temp_10K3DegF as an option under Action/Scale, depending onthe temperature units set up on the General tab.3. If you had selected the DischargeAirTemp_ option, in the additional settings, in theDATHiLimitSetpointDiff and DATLowLimitSetpointDiff fields, enter the discharge airtemperature high limit and low limit setpoints differentials respectively.4. (VAV application type only) If you had selected the InletAirTemp_ option, in the additionalsettings, in the BoxChangeoverTempDiff field, enter the box changeover temperaturedifference.5. (enteliWEB only) The Input Name field displays the object's name. You can change thisname by clearing the field and entering a new name.Multiple Space Temperature InputsYou can set up multiple SpaceTemp inputs and by default the algorithm will calculate theaverage of all inputs and assign that value to the AV1 object.Setting Up a Hardwired Occupancy InputThis topic describes how to set up an occupancy input using the Local Inputs tab on theconfiguration page.Occupancy inputs can either be maintained-contact or momentary contact types. Occupancyoverrides can share the same input as the temperature sensor.See the sequence of operations topic to learn more about occupancy modes in the algorithm.If you are setting up a LINKnet DNS-24L or eZNS network sensor to provide occupancyinput, use the LINKnet I/O tab on the configuration page.