enteliZONE Database Configuration ObjectsPage 78 of 84 eZV-440 Application GuideEdition 2.6Object Name ObjectRef Default DescriptionAirflow Setpoint AV830 0 CFM(VAV)0%(VVT)Current airflow setpoint reading (VAV)Damper position at this setpoint (VVT)Device Instance/ BACnet Address ObjectThe BACnet address is a unique address given to every controller and device in a Delta Controlsnetwork.You can set or change the enteliZONE controller’s BACnet address by writing to the AV97 object(BACnetAddress) in these versions:l eZ-440R4-230 controller firmware version 2.1 and higherl eZFC-424R4-24 controller firmware 2.2 and higherThe BACnet address can range from 1 to 4 million+. Since AV objects can only store 6 digits of theBACnet address, the seventh or millionth digit is stored in the AV97 description field.When a value is manually written to AV97 object, enteliWEB recognizes that the user is trying tosoftware address the controller and so DNA, if enabled, will automatically turn off. To turn DNAback on, you need to access the DEV object in enteliWEB and select the DNA checkbox.