enteliZONE Database Configuration ObjectsPage 74 of 84 eZV-440 Application GuideEdition 2.6Output Configuration ObjectsObject Name ObjectRef Default DescriptionTimePropClgMin AV150 0% The minimum cooling output value. The time-proportional algorithm scales the cooling outputusing this minimum value.TimePropClgMax AV151 100% The maximum cooling output value. The time-proportional algorithm scales the cooling outputusing this maximum value.TimePropHtgMin AV152 0% The minimum heating output value. The time-proportional algorithm scales the heating outputusing this minimum value.TimePropHtgMax AV153 100% The maximum heating output value. The time-proportional algorithm scales the heating outputusing this maximum value.TimePropPeriod AV154 100s The period of the pulse that is used to modulatethe time-proportional heating and cooling outputs.Heat1FanMin AV199 0 The optional fan speed interlock when duct Heat 1stage is running.Heat2FanMin AV200 0 The optional fan speed interlock when duct Heat 2stage is running.Heat3FanMin AV201 0 The optional fan speed interlock when duct Heat 3stage is running.Cool1FanMin AV202 0 The optional fan speed interlock when duct Cool 1stage is running.Cool2FanMin AV203 0 The optional fan speed interlock when duct Cool 2stage is running.HeatCoolLoad AV802 0 % Monitors if the system is in heating or coolingmode (<0 = cooling, >0 = heating).Heat1 AV803 100 % First heating stage.Heat2 AV804 0 % Second heating stage.Heat3 AV805 0 % Third heating stage.Cool1 AV806 0 % First cooling stage.Cool2 AV807 0 % Second cooling stage.AirflowDemand AV808 100 % VAV airflow demand.Fan1 AV810 0 % First fan stage.