LINKnet I/O TabPage 40 of 84 eZV-440 Application GuideEdition 2.6Function Select this option if:MonitoringOnly Input object BI1005 created but its value will not be used by theinternal algorithm.2. If you selected OccupancyDetection, in the additional settings, in the MotionOvrdTime field,enter how long the occupancy override should last. This setting allows the use of momentarycontact style occupancy signals.If you are using maintained-contact occupancy devices, enter zero in this field. In this case,occupancy statue is only based on contact position.Assign Functions to the Buttons and SliderSee Assigning Buttons and Slider Elements On eZNS-T100 Network Sensor.Set Up the LCD DisplayYou can select which icons are displayed on the network sensor's LCD screen.1. In the Display Options section, next to Occupancy, select the occupancy symbols you wouldlike displayed on the LCD screen.DisplayOption Select this option if you are setting up:NotDisplayed_ No occupancy status to be displayed.ManInHouse_ Occupancy status: when a room is occupied, the man in a house iconis displayed; when the room is unoccupied the icon changes so thatthe man appears outside the house. When the occupancy sensor isdisabled, neither icon is displayed.SunMoon_ Sun or Moon icon to be displayed. These icons can be used to showday and night occupancy modes.2. In the Display Setpoints, select how the setpoint of the current heating or cooling stage isdisplayed on the LCD screen.DisplayOption Select this option if you are setting up:On ButtonPressThe setpoint is displayed when the Temp Select, Temp Up or TempDown buttons are pressed.Always The setpoint is always displayed on the LCD in occupied mode.