eZV-440 Application GuideEdition 2.6Page 75 of 84Object Name ObjectRef Default DescriptionFan2 AV811 0 % Second fan stage.Fan3 AV812 0 % Third fan stage.DemandCtrlVent AV813 0 % Demand Control Ventilation. Its value reflects theCO2 demand (VAV/VVT).Custom1* AV815 0 % Custom stage associated with GCL controlledoutput.Custom2* AV816 0 % Custom stage associated with GCL controlledoutput.DamperCmd AV832 0 % Sets the damper position for theVentilationDamper output (VAV/VVT).Airflow Status BV800 Off_ Used to display the status of airflow in the duct(VAV/VVT).* Available only with enteliZONE programmable models.Setpoint Configuration ObjectsObject Name ObjectRef Default DescriptionOccHeating Setpoint AV100 21CelsiusBase heating setpoint in occupied modeOccCooling Setpoint AV101 24CelsiusBase cooling setpoint in occupied modeUnOccHeating Set-pointAV102 17CelsiusUnoccupied heating setpointUnOccCooling Set-pointAV103 21CelsiusUnoccupied cooling setpointHeatCoolChangeoverDelayAV104 5minutesTime delay between heating and cooling toprevent overshoot when the heating andcooling setpoints are close together. Rangebetween 1 to 30 minutes.Standby Setback AV105 1 Celsius Extra setpoint offset added in standby mode.