enteliZONE Sequence of OperationsPage 62 of 84 eZV-440 Application GuideEdition 2.6Setpoints and Occupancy ModesThe occupancy modes determine which temperature setpoints are used for the space.Occupied ModeIn occupied mode:Current heating setpoint = Occupied heating setpoint + Occupied setpoint offsetCurrent cooling setpoint = Occupied cooling setpoint + Occupied setpoint offsetIn occupied mode (with Eco Mode set up on network sensor or enabled using MV13 object):Current heating setpoint = Occupied heating setpoint + Occupied setpoint offset - Eco ModeSetbackCurrent cooling setpoint = Occupied cooling setpoint + Occupied setpoint offset + Eco ModeSetbackOccupant setpoint sits between the occupied heating and cooling setpoints. The occupied setpointoffset is restricted to be within the occupied setpoint offset range.In Eco Mode, the occupied setpoint offset range is relaxes by the amount specified by the EcoMode Setback.For night overrides, a pushbutton or motion override initiates the Night override mode.Standby ModeIn standby mode:Current heating setpoint = Occupied heating setpoint + Occupied setpoint offset - StandbySetbackCurrent cooling setpoint = Occupied cooling setpoint + Occupied setpoint offset + StandbySetbackIn standby mode (with Eco Mode set up on network sensor or enabled using MV13 object):Current heating setpoint = Occupied heating setpoint + Occupied setpoint offset - Eco ModeSetback - Standby SetbackCurrent cooling setpoint = Occupied cooling setpoint + Occupied setpoint offset + Eco ModeSetback + Standby SetbackUnoccupied ModeIn unoccupied mode:Current heating setpoint = Unoccupied heating setpointCurrent cooling setpoint = Unoccupied cooling setpoint