CommunicationEaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 41See Figure 18 on page 38 for the REPO location. Figure 21 shows a schematic of the REPO connectorcontacts.– Polarity2+ Polarity1REPOFigure 21. REPO Connector ContactsYou can set the REPO polarity. See the “REPO Input Polarity” setting in “User Settings” on page 28.Depending on user configuration, the pins must be shorted or open to keep the UPS running. To restart theUPS, reconnect (re-open) the REPO connector pins and turn on the UPS manually. Maximum resistance in theshorted loop is 10 ohm.Forced to Bypass StateIn the “Force to Bypass” state, the UPS transfers to Bypass model in every condition except frequencyconverter and generator mode.The following models have the REPO port configured for “Force to Bypass” function:Rack Modelsl PW9130G1000R-XL2UAUl PW9130G1500R-XL2UAUl PW9130G2000R-XL2UAUl PW9130G3000R-XL2UAUTower Modelsl PW9130G700T-XLAUl PW9130G1000T-XLAUl PW9130G1500T-XLAUl PW9130G2000T-XLAUl PW9130G3000T-XLAU.! IMPORTANTAlways test the REPO function before applying your critical load to avoid accidental load loss.Relay Output ContactsThe UPS incorporates three programmable relay outputs with potential free contacts for remote alarmindications: a standard relay port and two outputs in the RS-232 communication port. See Figure 18 onpage 38 for the locations of the ports. An additional four relay outputs can be obtained with the compatibleRelay Interface Card.Configure the relay outputs with the “Relay Configuration” setting in “User Settings” on page 28.WARNINGThe relay output contacts must not be connected to any utility connected circuits. Reinforcedinsulation to the utility is required. The relay output contacts have a maximum rating of 30 Vac/1Aand 60 Vdc/2A nominal values.