SpecificationsEaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 671500/1050 14 62 92 156 211750/525 34 130 212 355 442NOTE Battery times are approximate and vary depending on the load configuration and battery charge.Table 29. Battery Runtimes (in Minutes) at 100% Load (Tower Models) PF0.7Tower ModelsLoad (VA/Watts) Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMsPW9130L700T-XL700/490 8 N/A N/A N/A N/A525/368 12 N/A N/A N/A N/A350/245 21 N/A N/A N/A N/A175/123 37 N/A N/A N/A N/APW9130i700T700/490 8 N/A N/A N/A N/A525/368 12 N/A N/A N/A N/A350/245 19 N/A N/A N/A N/A175/123 35 N/A N/A N/A N/APW9130L1000T-XL1000/700 10 40 73 108 149750/525 13 58 101 152 219500/350 24 85 172 249 304250/175 48 190 310 451 569PW9130G1000T-XL / PW9130G1000T-XLEU / PW9130i1000T-XL1000/700 10 40 78 110 150750/525 13 55 103 151 223500/350 22 82 186 250 312250/175 47 190 328 431 584PW9130L1500T-XL1500/1050 7 34 63 88 1351125/788 11 44 84 129 210750/525 18 79 148 207 267375/263 38 167 278 475 540PW9130i1500T-XL1500/1050 7 32 61 98 1281125/788 11 47 83 126 195750/525 18 81 143 208 262375/263 38 171 298 416 564PW9130L2000T-XL (Estimated runtimes)2000/1400 15 61 111 156 1941500/1050 21 81 145 185 2691000/700 34 129 198 293 410Table 28. Battery Runtimes (in Minutes) at 100% Load (Rack Models) PF0.7 (Continued)Rack ModelsLoad (VA/Watts) Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs