SpecificationsEaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 68500/350 72 225 449 590 766PW9130G2000T-XL / PW9130G2000T-XLEU / PW9130i2000T-XL (Estimated runtimes)2000/1400 15 61 111 156 1861500/1050 21 81 145 184 2481000/700 34 129 198 293 431500/350 72 225 449 590 840PW9130L3000T-XL3000/2100 9 35 66 95 1322250/1575 13 53 100 139 1831500/1050 22 86 153 221 267750/525 69 168 298 395 545PW9130G3000T-XL / PW9130G3000T-XLEU / PW9130i3000T-XL (Estimated runtimes)3000/2100 9 36 68 101 1372250/1575 12 49 90 134 1651500/1050 20 79 143 180 240750/525 46 161 267 434 547NOTE Battery times are approximate and vary depending on the load configuration and battery charge.Table 30. BatteryInternal Batteries EBMsRackmountConfiguration7001000 VA models: 36 Vdc (3 12V, 9 Ah)1500 VA models: 48 Vdc (4 12V, 9 Ah)20003000 VA models: 72 Vdc (6 12V, 9 Ah)PW9130N1000R-EBM2U: 36 Vdc (2 x 3 12V, 9 Ah)PW9130N1500R-EBM2U: 48 Vdc (2 x 4 12V, 9 Ah)PW9130N3000R-EBM2U: 72 Vdc (2 x 6 12V, 9 Ah)TowerConfiguration700 VA models: 24 Vdc (2 12V, 9 Ah)1000 VA models: 36 Vdc (3 12V, 9 Ah)1500 VA models: 48 Vdc (4 12V, 9 Ah)20003000 VA models: 96 Vdc (8 12V, 9 Ah)PW9130N1000T-EBM: 36 Vdc (2 x 3 12V, 9 Ah)PW9130N1500T-EBM: 48 Vdc (2 x 4 12V, 9 Ah)PW9130N3000T-EBM: 96 Vdc (2 x 8 12V, 9 Ah)Fuses Not applicable (4) 30A/125 Vdc fuses per EBMTypeSealed, maintenance-free, valve-regulated, lead-acid,with minimum 3-year float service life at 25C (77F)Monitoring Advanced monitoring for earlier failure detection and warningRecharge Time (to90%)Internal batteries: 3 hours1 EBM: 9 hours; 2 EBMs: 15 hours; 3 EBMs: 21 hours; 4 EBMs: 27 hoursBattery Port External three-pole Anderson connector on UPS for connection to EBMTable 29. Battery Runtimes (in Minutes) at 100% Load (Tower Models) PF0.7 (Continued)Tower ModelsLoad (VA/Watts) Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs