b. Press the down arrow button to scroll to the TestBattery command. Press the ENTER button.The following message will appear: 082 TestBattery (CONFIRM).c. Press the ENTER key. The (TESTING...) messagewill appear. (The test duration is approximatelyfive seconds.)●● If the battery is OK, the (PASS) messagewill appear.●● If the battery is not OK, one of these messageswill appear:“ATTENTION – 1” indicates Battery Test Trouble*“ATTENTION – 2” indicates Battery Test Failed“ATTENTION – 3” indicates Battery TestCurrently Running“ATTENTION – 4” indicates Battery TestBlocked**d. The battery test results can be viewed by pressingthe down arrow. The following information will bedisplayed:VBat = XX.XX VoltsIBat = -X.XX Amps4. Verify the Control OK LED is illuminated on the controloperator panel. The AC POWER LED indicates thepresence of AC power (Figure 34).A B CX Y ZPHASE VOLTAGEALARMBATTERYAC POWERCONTROL OKFigure 34. Control OK and AC POWER LEDsotee:N The control includes a Power Save feature thatwill turn off the LEDs and backlit LCD display after15 minutes of inactivity at the front panel (no buttonspressed). The CONTROL OK and HOT LINE TAGLEDs are not affected by the power save mode.Pressing any key on the front panel will turn the LCDbacklight on and restore all LEDs to their current on/off states.All other tests described in this TESTINg section require theForm 4D pole-mount recloser control to be removed fromservice, connected to a bypassed recloser, or tested at alocation where the proper testing equipment is available.Alarm Conditione:●● During a battery test a 5Ω, 55 watt resistor is placedacross the battery terminals for approximately 5 seconds.The Form 4D control measures the battery voltage, ifthe voltage drops below 22.8 VDC the BATTERY LEDilluminates (Figure 34) and a battery alarm is issued, ifconfigured, at the end of the test.Remove the control from serviceIMPORTANTDisconnect switches for AC sensing and powerconnections are necessary to isolate the Form 4Dcontrol for testing and servicing.1. Enable GND TRIP BLOCKED to disable theground element.otee:N This prevents the control from tripping on imbalanceas the control cable is connected and disconnected.A. Press the GND TRIP BLOCKED button. The LEDshould be illuminated.CAuTIONHazardous voltage. Open CT secondaries can generatehigh voltages. Contact with CT pins of the disconnectedcable can cause electric shock and may result in personalinjury. Open recloser contacts and open disconnectswitches before disconnecting control cable. T204.3CAuTIONHazardous voltage. Cable conductors attached to controlswill remain at 53 vDC and 120/240 vAC potential whileconnected to the control. Contact with any pins atthe end of the cable directly or indirectly connectedto a control can result in personal injury or equipmentdamage. Disconnect battery and external power sourcesin the control then remove control cable at control endbefore disconnecting from recloser end. T312.22. Disconnect the 24V control battery.3. Disconnect control cable from control.4. Remove control AC sensing and power connectionsfrom the control.5. Disconnect any serial communications ports connections(Figure 35).6. Disconnect the ground from the control.* Battery Test Trouble indicates that the test results were not lower thanbattery failure voltage (15V) and not higher than the test voltage (22.8V).** Battery Test Blocked indicates a battery test was attempted with batterypower only. The battery cannot be tested when the control is poweredfrom the battery only (no AC power).37operation inStrUCtionS MN280049EN September 2017Form 4D Microprocessor-based pole-mount recloser control installation and operation instructions