6. If there are two batteries, remove the top battery anddual battery wire assembly. Otherwise, proceed to thenext step.7. Push up on the open notch-end of the bottom batterybracket to release one end.8. Remove the battery(s).otee:N Dispose expired batteries in an environmentallyresponsible manner. Consult local regulations forproper battery disposal.9. Place the replacement battery(s) in the location theprevious battery(s) were in.10. Re-install the battery brackets by sliding the open notch-end back into place (Figure 46).11. Tighten down the two thumb screws (Figure 46).12. Tighten down the two wing nuts for the batterybrackets (Figure 46).13. If there are two batteries, reconnect the dual batterywire assembly. Otherwise, proceed to next step.14. Reconnect control wiring to replacement battery(s)(Figure 44).15. Re-energize the control. Follow all locally approvedsafety procedures.16. Perform a battery test on the new battery(s) (assumingit has been adequately charged) to confirm the stateof the new battery(s) and wire assembly connections.Refer to Battery Test and Charging Proceduressection of this manual.ThumbScrewsWingNutsSliding open notch-enddown back into place.Figure 46. Reinstall battery bracket(s)Return the control to serviceAfter the required work is completed, proceed asfollowse:1. Remove AC power from the control.2. Disconnect the control battery.3. Disconnect the control from the test set.Follow this procedure to return the control to servicee:1. Appropriate personnel must verify that all controlsettings are correct.2. Reconnect the ground cable to the control.3. Control cable properly connected, fully tightened toensure gasket seal, and supported on both ends.4. Plug in the control battery.otee:N The Form 4D pole-mount recloser control will notautomatically power up until AC power is applied.5. Apply AC power to the control.6. Disable GND TRIP BLOCKED.A. Depress the GND TRIP BLOCKED button.7. Verify the control clock is set to the current time afterAC power has been reapplied.otee:N The control clock may require resetting if theoperating power has been disconnected for morethan thirty days. Refer to Service Information S280-104-2 Form 4D Microprocessor-Based RecloserControl Programming Guide for information onsetting the control clock.Additional proceduresusing removable insertsCAuTIONControl damage. De-energize both AC and DC powerprior to removing or installing any internal connectionsor circuit boards in the control. Failure to comply canresult in damage to the control. T241.11. Follow all locally approved safety procedures.2. De-energize both AC and DC power.A. Following established safety procedures, removeAC input power from TB1 or from AC inputreceptacle, if applicable.B. Disconnect the control wiring to the battery(s)(Figure 44).3. Loosen, but do not remove, the module swing panelground link 3/8” nuts with 3/8” nut driver (Figure 47).4. Use a 1/4” nut drive to loosen, but not remove, thethree (3) nuts from the retaining bar (Figure 47).5. Slide the retaining bar up to release the module.44 operation inStrUCtionS MN280049EN September 2017Form 4D Microprocessor-based pole-mount recloser control installation and operation instructions