6. Tilt back, but do not remove, the module from theswing panel (Figure 47).otee:N Rest the lower portion of the module on the swingpanel opening.Module swing panelground link nutsThree (3) retaining bar nutsFigure 47. Loosen retaining bar nuts and tilt module back7. Remove the existing insert(s) intended for replacementby pulling on the tab(s) that extend out of the side ofthe module (Figure 48).Figure 48. Remove existing insert8. Slide the new insert(s) into the module and align so thetext and LED slots are oriented in the window openingon the front panel.An electronic label template is included on the ProViewNXG application software CD and, once installed on yourPC, can be accessed through the following default address:C:\Program Files\Cooper\ProView NXG\Form 4D\Form 4DControl Customizable Inserts.doc.Two blank label templates are included with your control.9. Position the ground link on the swing panel to line upwith the ground lug on the module as it moves intoposition (Figure 49).Ground link nutFigure 49. Position the ground link on the swing panelto line up with the ground lug on the module10. Lift up on the module until the ground link slides intoplace and continue lifting up until the module is firmlyback into the swing panel.11. Press into place as necessary.12. Torque the nuts on the ground link to 24 in.-lbs.(Figure 49).13. Slide the retaining bar down all the way over themodule’s aluminum extrusion as much as possible.14. Torque the three (3) nuts to 24 in.-lbs. (Figure 47).15. Reconnect the battery (if used).16. Reconnect AC input power to TB1 or to AC inputreceptacle, if applicable.17. Verify the module powers up properly.Remove Existing ModuleCAuTIONEquipment misoperation. The control must be removedfrom service prior to performing any maintenance,testing, or programming changes and not (re)connectedto an energized recloser until all settings have beenverified. Failure to comply can result in equipmentmisoperation, equipment damage, and personal injury.g166.045operation inStrUCtionS MN280049EN September 2017Form 4D Microprocessor-based pole-mount recloser control installation and operation instructions