Appendix E72 Power Xpert Solar 1500/1670 kW Inverter MN141001EN—October 2014 www.eaton.comAppendix EFuse ReplacementThe following table summarizes the fuses that are used inthe inverter. Use only fuses that are the same part numberand value.Table 23. Inverter FusesFuseDesignator CabinetPurpose:Circuit/Wire/Component Association VoltageCurrent(A) Manufacturer PN Manufacturer WTN PNF1, F2 DC SS1 (DC Surge Suppressor) 1000 Vdc 20 PV20A-10F BUSSMANN 032-000800-0001Circuit: 10RD202/200 – F1Circuit: 10BK203/201 – F2F3 LC GFDI 5 A fuse 1500 Vdc 5 CC 1551 CPgRB 20x127/5MERSEN 032-000800-0023Circuit: 16BK204/206F4–F9 DC Pre-Charge Input Fuses 1000 Vdc 15 PV-15A10F BUSSMANN 032-000800-0017Circuit: 16RD210/211 – F4Circuit: 16BK214/215 – F5Circuit: 16RD218/219 – F6Circuit: 16BK222/223 – F7Circuit: 16RD226/227 – F8Circuit: 16BK230/231 – F9F10, F11, F12F65, F66, F67DC DC (PV) Voltage Sense Boards 1000 Vdc 1 PV-1A10F BUSSMANN 032-000800-0018VTB1-16RD235/234 – F10VTB1- 16BK236/244 – F65VTB2- 16RD238/237 – F11VTB2- 16BK239/245 – F66VTB3- 16RD241/240 – F12VTB3- 16BK242/246 – F67F13–F21 LC Filter-Capacitor Fuses: CO1/CO2/CO3 500 Vac 400 400NHG2B BUSSMANN 44-4445CO1- 3/0RD171 – F13 – 3/0RD162 – LO1ACO1- 3/0YL172 – F14 – 3/0YL163 – LO1BCO1- 3/0BU173 – F15 – 3/0BU164 – LO1CCO2- 3/0RD174 – F16 – 3/0RD165 – LO2ACO2- 3/0YL175 – F17 – 3/0YL166 – LO2BCO2- 3/0BU176 – F18 – 3/0BU167 – LO2CCO3- 3/0RD177 – F19 – 3/0RD168 – LO3ACO3- 3/0YL178 – F20 – 3/0YL169 – LO3BCO3- 3/0BU179 – F21 – 3/0BU170 – LO3C