5 RAMO5 motor starter5.6 LED indicatorsRapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 1275.6 LED indicatorsThe LEDs indicators of the RAMO5 motor control unit display the operatingstates and allow problems to be quickly diagnosed.LED State DescriptionFWD Clockwise rotating field of motor voltage (U–V–W)Off Not actuatedGreen enabled (RUN-Mode)Flashing(green)controlled:• but inhibited by the Quick stop function of sensor inputs I1 and I2• But blocked because when the supply voltage was switched on(400 V or ASi), the key switch was in the MANUAL position.→ A Reset command required.REV Counterclockwise rotating field of motor voltage (W–V–U)Only for reversing starter RAMO5-W…!Off Not actuatedGreen enabled (RUN-Mode)Green flashing controlled:• but inhibited by the Quick stop function of sensor inputs I1 and I2• But blocked because when the supply voltage was switched on(400 V or ASi), the key switch was in the MANUAL position.→ A Reset command required.AS-I AS-InterfaceDataOff ASi electronics have no supply voltage:Check ASi connection cablesCheck ASi power supply unit (head-end controller)Green Communication active, normal operationRed No communication:• Head-end controller (master) in STOP mode.• RAMO5 not entered or entered with the wrong address (ID).• RAMO5 in Reset mode.Yellow flas-hing, redASi address = 0→ Adjust ASi addressGreen,Red flashingfatal peripheral error, internal ASi errorFaultRed No data exchange, communication errorRed flashing Peripheral fault,I1 Sensor input SEN I1Off • not connected• not triggered (no input signal)Green SEN I1 triggered (input signal)REV OFF FWDPWR FLTSEN I1I1ACT Q1Q1SEN I2I2AS-I DataFaultOFF/RESET