1 Rapid Link 5 system1.5 Compliance with UL standards26 Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com1.5.3 RASP5RASP5 speed controllers have been tested in accordance with UL 61800-5and are approved as "listed".Table 5: RASP5Table 6: Short circuit current rating for individual and group protectionProperty ValueInput voltage 480 V ACOutput voltage, maximum 480 V ACRated operational voltage forbrake control180/207 V DC230/480 V AC400/480 V ACOutput current 2.5 A (RASP5-2…S1)4.3 A (RASP5-4…S1)5.6 A (RASP5-5…S1)8.5 A (RASP5-8…S1)Input current 2.4 A (RASP5-2...)4.1 A (RASP5-4...)5.3 A (RASP5-5...)7.8 A (RASP5-8...)Frequency 50/60 HzPhases 3Output frequency 0 - 320 HzField bus input voltage 30 V DCMotor protection integrated,at 105 % of full loadThermistor monitoring integratedProtection class NEMA 12 / NEMA 12KAmbient temperature, maximum 40 °C without fan55 °C with fanWith fuse (UL listed) Circuit-breaker (UL listed)With built-inrepair switchWithout built-in localdisconnectswitchWith built-inrepair switchWithout built-in localdisconnectswitchVoltage 480 V AC 480 V AC 480 V AC 480 V ACShort-circuit current, maximum 30 A 30 A 32 A 32 AInterrupting Rating 10 kA 65 kA 10 kA 10 kA→ Devices with an integrated repair switch are approved for use asmotor disconnects (lockout/tagout).