8 Parameter list8.4 Parameter groups for RASP5Rapid Link 5 · RAMO5 · RASP5 05/20 MN034004EN www.eaton.com 183P2-23 Auto ThermalManagementAutoThermalManagementIn case of too high temperature at the heatsink, the drivereduces the switching frequency set with P2-22 to reduce thelikelihood of an overtemperature trip.– 0 1 0P2-24 Start mode Defines the behaviour of the drive relating to the enablesensor input and also configures the automatic restart func-tion.0: Edge-r : Following power on or reset, the drive will not startif a start signal (FWD/REV) is still present. To start a risingedge is necessary.1: Auto-0 : Following a power on or reset, the drive will auto-matically start if a start signal (FWD/REV) is still present.2, .., 9: Auto-1 to 9 : Following a trip, the drive will make upto 9 attempts to restart at intervals set in P2-26. The drivemust be powered down to reset the counter. The number ofrestart attempts are counted, and if the drive fails to start onthe final attempt, the drive will trip, and will require the userto manually reset the fault.– 0 10 0P2-25 REAF start function Start function after an automatic restart0: Acceleration time (ramp)1: Spin Start2: According to P2-37– 0 2 0P2-26 Auto Reset Delay Auto reset delayDetermines the time that will elapse between consecutivedrive reset attempts when Auto Reset is enabled in P2-24.s 0.1 60 0.5P2-27 Action@Thermistor-fault MotorDevice reaction after “Thermistorfault Motor” occurs.Possibilities device dependent0: deactivated1: activated– 0 1 1P2-28 Service Interval Time Service Interval TimeDefines the number of operating hours, after which theservice indicator is shown on the display.If P2-29 = 1, the counter is set to the value defined here. Theremaining time until the next service is indicated with P0-22.h 0 60000 0P2-29 Reset ServiceIndi-catorReset Service IndicatorWith P2-29 = 1 the counter for the remaining hours until thenext service is set to the value defined in P2-28. Reset ofP2-29 to 0 is done automatically.– 0 1 0P2-30 Parameter set Restores factory parameter settings. – 0 1 0P2-31 Default selection Default settings, country specific.0: EU (Europe, 50-Hz networks)1: USA (North America, 60-Hz networks)– 0 1 0P2-32 Access key level2 Defines the password which is used to get access toextended parameter set (Level 2).Access via P1-14.– 0 65535 101P2-33 Parameter lock Determines whether to lock the parameters0: OFF. All parameters can be accessed and changed1: ON. Parameter values can be displayed, but cannot bechanged.If a remote keypad is connected, parameters cannot beaccessed (except P1-14 and P2-33).– 0 1 0Parameter Designation Description Unit Min Max DS