Maintenance and AlarmsEaton ePDU G3 Operation Manual P-164000277—Rev 5 128Type Code 0 or 1 (OS or System)! IMPORTANTFor Type Code 0 and Type Code 1, always contact customer support for assistance. These errorsare not user-correctable.The Type Code 0 and Type Code 1 alarms and events are triggered from the OS or the system. Figure 96provides an example of a Type Code 1 system alarm number code. It only contains an 5-digit identification code(no index code).Figure 96. Example Type 1 CodeTable 10 lists OS or System alarms and events.Table 10. OS or System Alarms and EventsTypeCode Identification Code Alarm or Event1 03073 Code unreachable1 03074 Heap overflow1 03075 Not enough memory in Heap1 02817 A command is sent to an unavailable device CAN1 02818 *Not used1 02819 Impossible to open a session with a CAN device1 02820 No answer from a CAN device1 02821 *Not used1 02822 The number of CAN devices discovered on CAN bus is too great1 02823 Command unknown1 02824 Device CAN Id out of range1 02825 Time duration of a command is too long1 02826 Report acquired from CAN device is wrong1 02827 Report descriptor acquired from CAN device is wrong1 01281 Mutex not available1 01282 HID object Id out of range1 01283 Report empty or not valid1 01284 Report Id out of range1 01285 Not enough memory in HEAP1 01286 Duration of the acquisition of Teridian is too long1 01282 HID object Id not in list of data saved in EEPROM1 02561 *Not used1 02562 *Not used1 0 2 8 2 0Alarm number code 102820: No answer from a CAN deviceIdentification Code = 02820Type Code = 1 (System)