Maintenance and AlarmsEaton ePDU G3 Operation Manual P-164000277—Rev 5 130Figure 97 provides an example of a Type Code 2 ePDU alarm number code.Figure 97. Example Type 2 CodeTable 11 lists ePDUand User alarms and events.Table 11. ePDU and User Alarms and EventsType CodeIdentification andIndex Code Alarm or Event Description2 201000 Dry Contact 1 Not Active The signal for Dry Contact 1 is active.2 201100 Dry Contact 1 Active The signal for Dry Contact 1 is not active.2 202000 Dry Contact 1 Open Dry Contact 1 is open.2 202100 Dry Contact 1 Closed Dry Contact 1 is closed.2 203000 Dry Contact 2 Not Active The signal for Dry Contact 2 is active.2 203100 Dry Contact 2 Active The signal for Dry Contact 2 is not active.2 204000 Dry Contact 2 Open Dry Contact 2 is open.2 204100 Dry Contact 2 Closed Dry Contact 2 is closed.2 205000 Sensor Probe Communication Failure Cleared Sensor Probe communication failure is cleared2 205100 Sensor Probe Communication Failure Sensor probe communication failure detected2 208000 Sensor Probe Not Connected Sensor probe not connected since firmware startup2 208100 Sensor Probe Connected Sensor probe connected at least once since firmwarestartup2 206000 Humidity No Threshold No humidity threshold has been triggered.2 206100 Humidity Warning Low Threshold The humidity level reading is less than the valueconfigured as the low humidity warning threshold.2 206200 Humidity Critical Low Threshold The humidity level reading is less than the valueconfigured as the low humidity critical threshold.2 206300 Humidity Warning High Threshold The humidity level reading is greater than the valueconfigured as the high humidity warning threshold.2 206400 Humidity Critical High Threshold The humidity level reading is greater than the valueconfigured as the high humidity critical threshold.2 207000 Temperature No Threshold No temperature threshold has been triggered.2 207100 Temperature Warning Low Threshold The temperature level reading is less than the valueconfigured as the low temperature warningthreshold.2 207200 Temperature Critical Low Threshold The temperature level reading is less than the valueconfigured as the low temperature critical threshold.2 207300 Temperature Warning High Threshold The temperature level reading is greater than thevalue configured as the high temperature warningthreshold.2 1 1 4 0 2Number code 211402: Eaton ePDU Critical Overcurrent L2 PhaseIdentification code = 114 Index code = 02Type code 2 = Eaton ePDU