InstallationEaton ePDU G3 Operation Manual P-164000277—Rev 5 33Figure 31. Connecting the EMP to the ePDU RJ-45 Serial Port Connector4. Use the mounting method appropriate to your installation to mount the EMP in a convenient locationanywhere on the rack.5. If desired, use cable ties to secure the Ethernet cable out of the way as needed.6. On startup, the ePDU automatically recognizes the EMP.Connecting the Output DevicesThe ePDU outlets are available for connecting and monitoring devices such as workstations, servers, andswitches. Connect a device you want to monitor to a power outlet on the ePDU with the power cord that comeswith the device.To connect your devices:1. Verify that each circuit breaker is in the On position.2. For ePDUs with detachable power cords. If the power cord is not connected, connect the power cord tothe ePDU. Otherwise, go to Step 3.3. Route the ePDU power cord toward a dedicated power source. If desired, use cable ties to secure thepower cord as needed. If the power cord must exit the rack cabinet to connect to a power source, use theopenings in the rack cabinet.4. Connect the power cord to a properly wired and grounded dedicated power source. The ePDU turns onand displays the Eaton startup screen while starting. After five seconds, the sequence of LCDscreensaver screens for this ePDU model begin cycling.5. Verify that no alarms display on the LCD. To resolve alarms, see “Maintenance and Alarms” on page 117.NOTE The maximum cable length is 2.99m (9.8 ft). If you install an EMP, theePDU serial port must be dedicated to the EMP.NOTE You may find it useful to document the connections you make.NOTE 1 Plug the ePDU into an appropriately rated outlet for its type.NOTE 2 Do not replace or rewire the power cord.